Heavy fuel oil storage infrastructure is defined by the product’s refusal to flow at ambient conditions. Every design decision, wall thickness, coil layout, metallurgy, insulation specification, traces back to the extreme temperature sensitivity of viscosity and the safety consequences of hydrogen sulfide generation in vapor spaces. This article walks through the engineering workflow from physical property analysis through tank standard selection, heating technology trade-offs, insulation detailing, internal hardware configuration, and the logistics chain that moves heated product from terminal to vessel.
You will learn how ISO 8217 viscosity grades translate into coil surface area calculations, why API 650 versus API 620 selection hinges on nitrogen blanketing pressure rather than temperature alone, how corrosion allowances split between liquid and vapor zones, and what drives the choice between steam, thermal oil, and electric tracing for a given tank diameter. The guide covers suction heater sizing for transfer viscosity targets, mixing nozzle placement to prevent stratification, sludge pocket geometry for cleanout access, and the documentation package required for custody transfer and MARPOL compliance.
HFO physical properties dictate every aspect of storage design from wall thickness to heating coil density. The extreme temperature sensitivity of viscosity requires tanks to maintain a narrow thermal band typically between 50 °C and 70 °C to ensure pumpability. Density variations between grades influence hydrostatic pressure calculations and mixing strategies. High sulfur content drives material selection for vapor spaces and dictates emissions control infrastructure. Singapore's total bunker sales reached a new high of 54.92 million tonnes in 2024 according to the Maritime and Port Authority of Singapore (MPA), underscoring the volume of product moving through infrastructure designed around these exact properties.
Viscosity grades define the heating duty required to reach transfer viscosity. ISO 8217 residual grades such as RMG 380 and RMK 700 indicate kinematic viscosity at 50 °C in centistokes. A typical RMG 380 may exceed 50,000 cSt at ambient temperature but drops below 200 cSt at 60 °C which is the common pumpability target. This exponential relationship means a 5 °C drop can double viscosity and stall positive displacement pumps. Heating systems must therefore deliver uniform heat flux to avoid cold spots where viscosity spikes locally. Designers use the Walther equation or ASTM D341 charts to model the viscosity temperature curve for each specific batch because crude source and blending components shift the curve significantly.
Pour point establishes the absolute minimum temperature before the fuel ceases to flow as a continuum. Heavy fuel oils typically exhibit pour points between 30 °C and 40 °C depending on wax content and asphaltene stability. Storage temperature must remain at least 10 °C above the pour point to prevent gelation in suction lines and dead zones. If a tank cools below this threshold during a prolonged outage the entire inventory may require remediation with cutter stock or extended recirculation through external heat exchangers. Pour point depressants are rarely used in bulk storage because dosage economics favor thermal management. Cold flow behavior also informs insulation thickness specifications for roof and shell courses.
Density variations drive hydrostatic load calculations and create stratification risks in tall tanks. HFO density at 15 °C ranges from 920 kg/m³ for lighter residual grades to over 1010 kg/m³ for dense cracked residues. At operating temperature density drops by roughly 0.7 kg/m³ per degree Celsius. In a 20 m high tank this thermal gradient can create a 15 kg/m³ density difference between hot oil near coils and cooler oil at the roof promoting layering. Stratification prevents representative sampling and causes suction heaters to draw overheated product while sludge accumulates in cooler lower zones. Mechanical mixers or eductor nozzles are specified to maintain homogeneity especially when blending cutter stock into the tank.
Sulfur content dictates vapor space metallurgy and safety systems. High sulfur fuel oil typically contains 1.5 to 3.5 percent sulfur by weight according to the International Maritime Organization (IMO) (2020). At storage temperatures above 60 °C microbial sulfate reduction and thermal cracking can generate hydrogen sulfide concentrations exceeding 100 ppm in the headspace. This requires tank roof plates and internal floating roof components to be fabricated from killed carbon steel with a minimum 3 mm corrosion allowance or upgraded to 316L stainless steel for critical fittings. Fixed roof tanks must incorporate inert gas blanketing or vapor recovery units to prevent H2S accumulation. Personnel entry procedures mandate continuous H2S monitoring because the gas is heavier than air and collects at the tank bottom.
Tank design standards and material selection ensure structural integrity under thermal cycling and corrosive vapor conditions. API 650 governs welded atmospheric storage tanks up to 2.5 psig design pressure while API 620 covers low pressure tanks up to 15 psig suitable for heated HFO with nitrogen blanketing. Carbon steel ASTM A36 or A516 Grade 70 forms the baseline material with corrosion allowances calculated for both liquid phase and vapor phase attack. Foundation design must accommodate thermal expansion of the shell which can grow 15 mm in diameter over a 40 °C temperature rise. Singapore's total bunker sales grew 6.0% year-on-year in 2024 according to the Maritime and Port Authority of Singapore (MPA), driving demand for new tankage built to these codes.
API 650 applies to the majority of hFO Storage Tank Design, Heating & Transport Logistics operating at atmospheric pressure with open vents or pressure vacuum valves. The standard limits design metal temperature to -29 °C minimum which is adequate for heated service. API 620 is selected when the tank requires internal pressure above 2.5 psig such as when nitrogen blanketing maintains a positive pad of 5 to 8 psig to exclude air and reduce H2S oxidation. API 620 also permits lower design metal temperatures down to -168 °C with impact tested materials though this is rarely relevant for HFO. The choice affects shell thickness calculations because API 620 uses a more rigorous stress analysis allowing thinner plates for the same diameter. Both standards require hydrostatic testing after erection.
Carbon steel grade selection balances cost weldability and notch toughness at operating temperature. ASTM A36 is permitted for shell thickness up to 25 mm in API 650 but many owners specify ASTM A516 Grade 70 normalized for improved toughness and consistent through thickness properties. For shell courses above 40 mm ASTM A516 Grade 70 with Charpy V notch testing at 0 °C is standard practice to prevent brittle fracture during emergency cooldown. Roof plates exposed to H2S laden vapor often upgrade to ASTM A516 Grade 70 with HIC resistant chemistry per NACE MR0103. All plate material must carry mill certificates showing heat analysis and mechanical properties traceable to the tank drawing.
Corrosion allowance accounts for general wall loss in both liquid and vapor zones. A typical allowance of 3 mm is added to the calculated shell thickness for the bottom 3 m of shell course where water bottoms and microbial activity concentrate. The vapor space above the liquid level receives a 2 mm allowance for H2S condensation corrosion. Cathodic protection is mandatory for tank bottoms in contact with soil or concrete. Impressed current systems with mixed metal oxide anodes in concentric rings provide uniform current distribution. Reference cells embedded in the sand pad allow potential monitoring. The system is designed for 20 mA/m² current density with a 20 year anode life. Isolation joints on piping prevent current drainage.
Foundation design for heated tank loads addresses thermal expansion differential settlement and anchor bolt forces. A ringwall foundation with a minimum width of 1.2 m supports the shell and distributes the load to a bearing capacity of typically 150 kPa. The tank bottom rests on a sand bitumen cushion 50 mm thick to accommodate radial growth of the shell during heating cycles. Anchor chairs are designed for uplift from wind and seismic loads combined with thermal stress in the shell. Stainless steel shims under anchor chairs prevent galvanic corrosion. The foundation includes embedded heating cable conduits for trace heating of the bottom plate periphery to prevent cold spots where product could solidify against the chilled concrete.
Steam coils deliver the highest heat flux for large diameter tanks but require boiler infrastructure and condensate return systems. Thermal oil systems operate at lower pressures up to 300°C without phase change, reducing safety valve maintenance and enabling precise temperature control for viscosity sensitive grades. Electric tracing suits smaller tanks or remote sites lacking steam generation, though operating costs rise sharply above 500 kW installed capacity. The choice hinges on existing utility infrastructure, tank diameter, and the viscosity target at the suction nozzle. Sales of alternative bunker fuels in Singapore exceeded one million tonnes for the first time, reaching 1.34 million tonnes in 2024 according to the Maritime and Port Authority of Singapore (MPA), reflecting a shift in terminal heating demand profiles.
Coil surface area is calculated using the overall heat transfer coefficient U, the log mean temperature difference LMTD, and the total heat duty Q required to overcome heat losses plus the sensible heat for heat-up. For maintenance heating Q equals the steady state heat loss through insulation at the design ambient temperature. For heat-up duty Q includes the tank steel mass, product mass, and specific heat capacities multiplied by the allowable temperature rise rate. Typical U values range from 150 W/m²K for steam coils in heavy fuel oil to 80 W/m²K for thermal oil coils. Fouling factors of 0.0002 m²K/W are added for HFO service. The coil layout follows a helical or grid pattern covering 60 to 70 percent of the tank floor area to ensure uniform bulk temperature.
Maintenance temperature holds the bulk product between 50°C and 70°C to prevent solidification and keep viscosity below 500 cSt for recirculation pumps. Transfer heating raises the suction zone to 90°C to 100°C, dropping viscosity below 100 cSt for positive displacement loading pumps and custody transfer metering. A dedicated suction heater or steam lance at the nozzle provides this localized boost without heating the entire inventory. Dual setpoint controllers on the thermal oil or steam supply valve manage the transition. The temperature differential between maintenance and transfer modes dictates the coil surface area margin, typically 25 percent above maintenance duty.
Heat-up time from cold start governs the peak heating capacity. A typical 50,000 m³ tank requires 48 to 72 hours to raise 380 cSt HFO from 20°C to 60°C maintenance temperature using the maintenance coil bank alone. Accelerated heat-up to 24 hours demands a 2.5x coil area increase or supplemental portable steam lances. The heat-up curve is non-linear; the first 20°C rise is rapid due to high LMTD, while the final approach to target slows as product viscosity drops and natural convection improves. Thermal stress in the shell and bottom plate limits the maximum allowable metal temperature gradient to 30°C per hour per API 650 Annex M.
| Parameter | Steam Coils | Thermal Oil Coils | Electric Tracing |
|---|---|---|---|
| Typical U Value (W/m²K) | 150 | 80 | 40 |
| Max Supply Temperature (°C) | 200 (saturated) | 300 | 250 (sheath) |
| Pressure Rating (barg) | 10-15 | 5-10 (pump head) | N/A |
| Control Precision (°C) | ±5 | ±1 | ±2 |
| Maintenance Intensity | High (traps, leaks) | Medium (fluid analysis) | Low (element replacement) |
| Suitability | Large tanks >20,000 m³ | Medium tanks, precise control | Small tanks <5,000 m³, remote |
The table compares the three dominant heating technologies across six engineering parameters. Steam coils provide the highest heat transfer coefficient U at 150 W/m²K, minimizing surface area for large tanks, but require condensate management and trap maintenance. Thermal oil offers superior control precision at ±1°C and operates at lower pressure, reducing mechanical risk, though fluid degradation requires annual analysis. Electric tracing has the lowest U value at 40 W/m²K, limiting use to smaller volumes, but eliminates boiler house capital expenditure. Selection matches the tank diameter, utility availability, and the viscosity window required for the specific HFO grade handled.
Mineral wool remains the standard for tank walls and roofs, offering thermal conductivity of 0.040 W/mK at 50°C mean temperature, fire resistance to 750°C, and vapor permeability that allows moisture escape. Rigid polyurethane foam (PUF) achieves 0.024 W/mK, reducing thickness by 40 percent, but requires a fire rated covering and is limited to 110°C continuous service. Cellular glass provides 0.048 W/mK with zero water absorption and compressive strength of 700 kPa, making it the only viable option for tank bottoms under hydrostatic load. Singapore's LNG bunker sales rose from 0.11 million tonnes in 2023 to 0.46 million tonnes in 2024 according to the Maritime and Port Authority of Singapore (MPA), driving cryogenic insulation specifications that influence dual-service terminal designs.
Thickness is calculated to limit heat loss to 10 W/m² for walls and 7 W/m² for roofs at the design maintenance temperature and minimum ambient. The formula uses the thermal resistance R = thickness / conductivity, solving for thickness given the overall U value target. For a 60°C maintenance temperature and -10°C ambient, mineral wool requires 200 mm on walls and 250 mm on roofs. PUF achieves the same loss at 120 mm and 150 mm respectively. Cellular glass at the bottom requires 100 mm under the floor plates to limit ground heat loss to 5 W/m². Thicknesses are rounded up to the nearest 50 mm standard board size.
Roof insulation uses staggered double layer mineral wool boards with offset joints, mechanically fixed to the deck with insulation anchors and covered by a galvanized steel weather jacket. Wall insulation employs vertical mineral wool batts wired to horizontal stiffener rings at 1 m centers, protected by profiled aluminum cladding with overlapped seams. Floor insulation places cellular glass boards on a leveled sand bitumen bed, joints sealed with bitumen mastic, topped by a reinforced concrete screed or steel bottom plate with a vapor barrier. The roof to wall junction uses a tapered insulation wedge to eliminate thermal bridging at the knuckle.
Weatherproofing relies on a continuous vapor barrier on the cold side of the insulation to prevent moisture ingress that degrades thermal performance. Aluminum foil faced mineral wool or a separate 200 µm polyethylene membrane serves as the barrier, with all penetrations sealed by silicone boots and stainless steel clamps. Cladding seams are lapped 100 mm and sealed with butyl tape. Roof penetrations for vents, gauges, and manholes use insulated curb flashings with counter flashing integrated into the cladding system. Annual infrared thermography surveys identify wet insulation sections for targeted replacement before corrosion under insulation initiates.
Suction heater bundles maintain the oil immediately surrounding the pump inlet at the required discharge viscosity typically 100 to 200 cSt. Steam or thermal oil coils are arranged in a vertical U-tube or hairpin configuration mounted directly on the suction nozzle flange inside the tank. The heating surface area is calculated using the heat loss from the suction pipe plus the energy needed to raise the bulk oil from the minimum storage temperature to the pumping viscosity within the required startup window. A typical 300 mm suction line requires 15 to 25 m² of coil surface for heavy grades. Coils are fabricated from Schedule 80 carbon steel with 25 mm outer diameter tubes spaced to allow sludge settlement between passes without bridging.
Mixing nozzles prevent stratification and blend fresh receipts with heel stock by creating a high velocity jet that entrains surrounding oil. Eductors are positioned at the tank bottom radius opposite the suction nozzle to sweep the floor toward the outlet. A minimum of two nozzles per 30 m tank diameter are installed at 0.5 m above the floor plate angled 15 degrees upward. They operate on a recirculation loop driven by a dedicated low shear pump or the main transfer pump during receipt. Flow rates target three tank turnovers per 24 hours during blending. Nozzle tips are hardened stainless steel to resist erosion from catalytic fines present in residual fuels.
Vortex breakers suppress air core formation at the suction inlet when the liquid level drops near the nozzle. A cruciform plate assembly welded to the nozzle flange extends horizontally 1.5 times the nozzle diameter in each direction with a vertical clearance of 300 mm above the nozzle centerline. For tanks operating with low submergence the breaker incorporates a perforated shroud that forces flow to enter horizontally breaking the vortex before it reaches the pipe. The open area ratio of the shroud exceeds 4:1 relative to the nozzle cross section to minimize pressure drop. Stainless steel construction prevents corrosion debris from restricting the openings during long service intervals.
Sludge pockets collect water sediment and catalytic fines that settle during storage allowing clean product withdrawal. The pocket is a dished depression 300 mm deep centered under the suction nozzle with a 1:10 slope from the tank floor to the pocket center. A dedicated 150 mm cleanout nozzle with a blind flange provides access for vacuum extraction during planned shutdowns. A flush connection on the pocket nozzle allows high pressure water or cutter stock injection to mobilize hardened sludge before mechanical removal. The pocket floor is clad with 6 mm stainless steel overlay to resist abrasion during cleaning operations.
Pump selection for HFO transfer hinges on viscosity range flow stability and suction conditions. Triple screw pumps handle viscosities up to 50,000 cSt with smooth pulse free flow and high volumetric efficiency making them the default for main transfer duty. External gear pumps suit lower viscosity grades below 5,000 cSt and metering applications but suffer from bearing wear with abrasive contaminants. Centrifugal pumps are limited to viscosities below 1,500 cSt and require oversized impellers and reduced speeds to maintain efficiency. The table below compares key selection parameters for typical terminal service.
| Parameter | Triple Screw Pump | External Gear Pump | Centrifugal Pump |
|---|---|---|---|
| Viscosity Range (cSt) | 100, 50,000 | 50, 5,000 | 10, 1,500 |
| Max Differential Pressure (bar) | 40 | 25 | 15 |
| Flow Pulsation | Near Zero | Low | None |
| NPSH Required (m) | 2, 4 | 3, 5 | 4, 8 |
| Solids Tolerance | Moderate | Low | High |
| Typical Speed (rpm) | 1,450, 1,750 | 950, 1,450 | 1,450, 2,900 |
The table shows triple screw pumps dominate high viscosity service due to low NPSHr and minimal pulsation. Gear pumps fill a niche for lighter grades and blending metering. Centrifugal units appear only in booster roles where viscosity is reduced by pre heat. NPSHr values assume 50°C inlet temperature; colder starts increase requirements significantly. Speed selection balances mechanical wear against pump size and capital cost.
NPSH available for hot HFO accounts for vapor pressure at pumping temperature static head friction loss and acceleration head in the suction piping. Vapor pressure of 380 cSt residual fuel at 100°C is approximately 0.03 bar absolute rising to 0.15 bar at 130°C. Static head is the vertical distance from minimum operating level to pump centerline minus 0.3 m safety margin. Friction loss uses the Darcy Weisbach equation with viscosity corrected Reynolds number; a 300 mm suction line at 200 m³/h and 200 cSt incurs 0.15 bar per 10 m equivalent length. Acceleration head for reciprocating pumps adds 0.5 to 1.0 m but is negligible for screw pumps. Total NPSHa must exceed NPSHr by 1.0 m minimum at the maximum continuous flow rate.
Variable frequency drives allow pump speed modulation to match viscosity changes during startup grade changes or tank heel conditions. Reducing speed from 1,750 rpm to 1,200 rpm lowers flow proportionally while cutting power consumption by the cube of the speed ratio. This prevents motor overload during cold starts when viscosity may exceed 10,000 cSt. The drive ramp profile is programmed to limit torque rise to 150 percent of rated torque protecting the coupling and gear reducer. Closed loop control using a discharge pressure transmitter maintains constant header pressure as viscosity varies. Harmonic filters are specified for drives above 110 kW to meet IEEE 519 limits at the point of common coupling.
Pump relief valves protect positive displacement pumps from overpressure during blocked discharge or valve closure. The valve is mounted directly on the pump discharge flange with a set pressure 10 percent above the maximum discharge pressure. The recirculation line returns flow to the tank suction heater zone or a dedicated mixing nozzle not the pump suction to avoid heat buildup. Line size matches the pump discharge diameter minimum 100 mm. A thermal relief valve on the recirculation line prevents pressure lock from solar heating when the main line is isolated. All relief valves are pilot operated for tight shutoff and minimal simmer with stainless steel trim for HFO service.
Trade Fuel Oil & Petroleum Products on Global Trade Plaza: petroleum by products on Global Trade Plaza, petroleum by products suppliers and exporters, petroleum by products buyers and importers, virgin fuel oil d6, petroleum oil related products on Global Trade Plaza, low pour fuel oil lpfo, liquefied petroleum gas lpg, low pour fuel oil lpfo.
Related reading: LPFO vs HFO: Specifications, Grades & Trading Differences, D6 Virgin Fuel Oil Specifications: Quality Data Sheet.
Design every HFO tank around the non-negotiable thermal band of 50°C to 70°C, selecting API 650 for atmospheric service or API 620 when nitrogen blanketing at 5, 8 psig is required for H2S control. Specify ASTM A516 Grade 70 with Charpy testing at 0°C for shell courses above 40 mm, apply a 3 mm corrosion allowance in the bottom liquid zone and 2 mm in the vapor space, and install impressed current cathodic protection at 20 mA/m² with a 20-year anode life. Size heating coils using the Walther equation for the specific batch viscosity curve, choosing steam for highest flux in large tanks, thermal oil for ±1°C precision, or electric tracing only for small diameters. Insulate walls to a 10 W/m² loss target using 200 mm mineral wool, 120 mm polyurethane, or 100 mm cellular glass under floor plates, and fit eductor nozzles or mechanical mixers to prevent stratification in tanks over 15 m tall.
Equip suction heaters to guarantee discharge viscosity below 200 cSt, verify pre-heat temperatures with inline viscometers before custody transfer, and document the complete chain, ISO 8217 grade certificate, MARPOL bunker delivery note, heating logs, and tank calibration tables, for compliance. Plan cleaning cycles around sludge pocket geometry, estimating sludge volume for disposal manifests. For procurement of compliant steel, coils, insulation, or cathodic materials, search verified suppliers on Global Trade Plaza or consult engineering contractors listed through trade associations and classification society registers.
HFO must be maintained between 50°C and 70°C to keep viscosity below 500 cSt for reliable pumpability. The exact setpoint depends on the ISO 8217 grade; RMG 380 typically targets 60°C to achieve roughly 200 cSt at the suction flange. Storage temperature must also stay at least 10°C above the pour point to prevent gelation in suction lines.
Calculate the total heat duty required to offset steady-state losses through insulation and to raise product temperature during heat-up, then divide by the steam coil heat transfer coefficient of approximately 150 W/m²K and the log mean temperature difference. Use the Walther equation or ASTM D341 charts to confirm viscosity at the target temperature. Add a 10 to 15 percent safety factor for fouling and coil aging.
API 650 governs atmospheric tanks up to 2.5 psig with open vents or pressure-vacuum valves. API 620 applies when nitrogen blanketing requires internal pressures of 5 to 8 psig to exclude air and suppress H2S oxidation. API 620 uses a more rigorous stress analysis allowing thinner plates for the same diameter and permits lower design metal temperatures with impact-tested materials.
Positive displacement screw pumps or gear pumps are standard for high viscosity HFO transfer because they deliver constant flow regardless of pressure variations. Centrifugal pumps lose efficiency sharply above 500 cSt and require oversized impellers. Select screw pumps with hardened rotors and casing materials compatible with fuel oil; ensure NPSH available exceeds NPSH required by at least 0.5 m at operating viscosity.
Roof insulation targets a maximum heat loss of 10 W/m²; mineral wool requires approximately 200 mm, polyurethane foam 120 mm, and cellular glass 100 mm. Roof heat loss is critical because the vapor space temperature controls H2S condensation rates on roof plates. Verify the selected thickness against the thermal conductivity at the mean operating temperature of 60°C.
ISO tank containers require pre-heating to a minimum of 50°C, typically 60°C, to achieve a discharge viscosity below 500 cSt before connecting the discharge hose. Verify the product temperature at the container bottom outlet using a calibrated probe; do not rely solely on the heating coil inlet temperature. Allow 24 to 48 hours for a cold 20-foot container to reach uniform temperature using steam or thermal oil coils.
Estimate sludge volume based on tank capacity per year of service, adjusted for fuel stability and water bottom accumulation. Use manual dipping with sludge gauge tapes or ultrasonic profiling through roof nozzles to map the sludge profile before cleaning. Confirm volume by measuring the thickness at multiple radial positions and calculating the conical or flat-bottom geometry.
Nitrogen blanketing pressure is typically maintained at 5 to 8 psig (0.35 to 0.55 barg) on API 620 tanks to maintain a positive pad that excludes atmospheric oxygen and reduces H2S formation in the vapor space. The regulator setpoint must exceed the maximum operating vacuum of the pressure-vacuum valve and the maximum liquid head during filling. Monitor pad pressure continuously with a low-pressure alarm at 3 psig.
H2S forms through microbial sulfate reduction and thermal cracking at storage temperatures above 60°C in high sulfur fuel oil. Concentrations can exceed 100 ppm in the headspace. Monitor continuously with fixed H2S detectors at the roof manway and tank bottom because the gas is heavier than air; require personal multi-gas monitors for any confined space entry.
API 2350 mandates a documented overfill protection system with independent high-level alarms, automatic transfer shutdown, and defined response procedures for each tank. For heated HFO, the level instrumentation must be rated for the operating temperature and vapor space corrosion. Conduct a risk assessment per Section 5 to set the high-high alarm level below the maximum fill height accounting for thermal expansion of the product.
Size the vapor recovery unit based on the maximum loading rate multiplied by the vapor generation factor for HFO at loading temperature, typically 0.5 to 1.0 Nm³ vapor per m³ liquid loaded. Select a unit rated for H2S concentrations up to 200 ppm and hydrocarbon dew point at operating pressure. Include a knockout drum upstream to remove condensed heavy ends and a thermal oxidizer or carbon bed for final treatment.
Use alcohol-resistant aqueous film forming foam (AR-AFFF) 3x3 or 1x3 concentrate listed for hydrocarbon and polar solvent fires at an application rate of 6.5 L/min/m² for a minimum 65-minute duration per NFPA 11 and API 2030. HFO fires require higher application rates than crude oil due to the elevated storage temperature and potential for boil-over if water contacts the hot product. Ensure foam chambers and pourers are rated for the tank diameter and roof type.